Flatkabel PVC Svart 4G0.75 mm²
Lägg till en bevakning så meddelar vi dig så snart varan är i lager igen.
Flatkabel PVC Svart 4G0.75 mm²
Flatkabel
Flatkabel PVC lämpar sig i rörliga applikatoner som kran- och hissinstallationer.
En flatkabel är platseffektiv i jämförelse med konventionella runda kablar, vilket gör de idealliskt för utrymmesbesparande applikationer.
Technical Data
Special PVC-flat cable adapted to EN 50214 / DIN VDE 0283-2
flexing -5°C to +70°C
fixed installation -40°C to +80°C
Nominal voltage: up to 1 mm² U0/U 300/500 V, from 1,5 mm² U0/U 450/750 V
Test voltage: up to 1 mm² 2000 V, from 1,5 mm² 2500 V
Bending radius: 10x cable thickness
Cable Structure
Bare copper-conductor, to DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5
Core insulation of PVC compound type TI2 to DIN VDE 0207-363-3 / DIN EN 50363-3
Core identification to DIN VDE 0293- up to 5 cores coloured- from 7 cores, black with continuous white numbering
Cores laying parallel
GN-YE conductor
Outer sheath of special PVC compound type TM2 to DIN VDE 0207-363-4-1/DIN EN 50363-4-1
Sheath colour black (RAL 9005)
Properties
Extensively oil resistant, oil-/ chemical Resistance - see table Technical Informations
Extremely small bending radius
High flexibility
Minimum waste of space
Packeting possibility
Tests
PVC self-extinguishing and flame retardant acc. to DIN VDE 0482-332-1-2, DIN EN 60332-1-2,
IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B)
Notes
Part no. 27012 (6x4).
G = with green-yellow conductor
AWG sizes are approximate equivalent values. The actual cross section is in mm².
Application
Installation notes Cables reels with flat cables must be transported in standing position on the flange. A bending flexibility can be achieved on a plane surface. For this purpose, the corresponding fitting instructions should be followed.
• Put the cable trolly on the guiding rail or upon carrier beam and push them together at the starting point. The distance between the bedding surface of two cable trollys must be wider than the double thickness of a cable-packet.
• During the packeting performance, it must be started with the smaller cross section which lays on the bedding surface and will be builded successively so that the biggest cross section is laying on the top.
• Further, be careful of a symmetrical load distribution.
• In case of multicore flat cables with small cross section, smaller than 2,5 mm², is very critical due to its low tensile stress.
In such case, you should add 10% reserve wire for calculation. = Product conforms with EC Low-Voltage Directive 2006/95/EC.